By using our site you agree that we use cookies. More OK

D4TB, D4TF - Three-phase transformers

with 4% uk
Three-phase transformer: DTF / D4TB, D4TF / DTSP / DTFSP

Contact
Tel.: +43 / 2689 / 2744 – 0
E-mail: info@trafomodern.com

Designed and tested according

  • IEC/EN 61558-2-1 / EN 60076-11

Typical applications

  • Inverter applications

Basic equipment

  • Separate windings
  • Insulation class B / F 25 kVA
  • Ambient temperature –25 to 40 °C
  • Connection terminal (<=115 A)
  • Frequency 50/60 Hz
 
  • Static shield windings is additional shielding between primary and secondary sides.
    For versions with increased climate resistance, the transformers is supplied with a specially insulated finish.The finish enables the transformer to be used in areas of high humidity.
    Transformer version with reinforced insulation upon request.
     
  • CUR according to EIS 130 or EIS 155 to OBJY2. or OBJY8.E160829 (Systems, Electrical Insulation - Component bzw. Systems, Electrical Insulation Certified for Canada - Component)

When ordering, the following information must be added to the type designation:

D4TF(*/*)*

1st place holder  ≙ rated input voltage
2nd place holder ≙ rated output voltage
3rd place holder ≙ vector group

Sample order

  • requested type D4TB20
  • requested rated input voltage 400 V
  • requested rated output voltage 320 V
  • requested vector group Yd5

The correct type designation reads D4TB20 (400/320) Yd5

The unambiguous article number of your configuration will be defined by trafomodern during the offer- and order process.

  Here is a hidden table in the mobile version. Click here to display it.
Type rating for use according to insulation class1) Rated input voltage Rated output voltage Type Price per unit Price for currents up to Cu-factor 2) Copper surcharge
B kVA  F kVA V (selectable) V (selectable)   Euro A   Euro
4,0 - 50-1000 50-1000 D4TB4,0(*/*)* 750,30 25 15,00 75,21
5,0 -     D4TB5,0(*/*)* 904,90   11,90 59,66
6,3 -     D4TB6,3(*/*)* 1.026,90   10,00 50,14
8,0 -     D4TB8,0(*/*)* 1.343,10 63 11,00 55,15
10,0 -     D4TB10,0(*/*)* 1.663,00   13,50 67,69
12,5 -     D4TB12,5(*/*)* 1.929,30   14,90 74,71
16,0 -     D4TB16,0(*/*)* 2.324,00   26,40 132,36
20,0 -     D4TB20,0(*/*)* 2.859,10   38,30 192,03
- 25     D4TF25,0(*/*)* 3.027,20   38,50 193,03
- 32     D4TF32,0(*/*)* 3.425,30   39,50 198,05
- 40     D4TF40,0(*/*)* 4.087,10 100 51,00 255,70
- 50     D4TF50,0(*/*)* 4.926,50   72,80 365,00
- 63     D4TF63,0(*/*)* 5.467,60   61,40 307,85
- 80     D4TF80,0(*/*)* 6.603,90 200 110,00 551,52
- 100     D4TF100,0(*/*)* 7.818,70   120,00 601,66

1) Rated output when used according to insulation class B, maximum of 130° C; for insulation class F maximum of 155° C
2) The calculation method of the material price surcharge will be explained in Section 2.1 in the general conditions of busines


D4TB, D4TF grafic - Three-phase transformer with 4% uk

Here is a hidden table in the mobile version. Click here to display it.
Type Total
weight
No-
load
losses
Short-
circuit
losses*
Short-
circuit
voltage
Efficiency
factor
a b b1 c c1 e f ø g
  kg W W %                  
D4TB4,0 31 45 210 ≥4 0,88 300 154 147 290 260 224 119 10 x 18
D4TB5,0 45 40 270 ≥4 0,9 300 193 162 334 260 224 134 10 x 18
D4TB6,3 55 60 315 ≥4 0,9 390 184 152 384 310 350 126 10 x 18
D4TB8,0 70 75 340 ≥4 0,91 390 199 167 384 310 350 141 10 x 18
D4TB10,0 95 95 505 ≥4 0,92 450 204 172 434 360 400 142 13 x 20
D4TB12,5 95 95 490 ≥4 0,96 450 204 172 434 360 400 142 13 x 20
D4TB16,0 115 120 650 ≥4 0,97 450 264 232 434 360 400 202 13 x 20
D4TB20,0 150 130 720 ≥4 0,97 540 267 - 496 - 450 197 14 x 20

Dimensional drawings for D4TF25,0 to D4TF100 available on request
all dimensions in mm