STA - Single-phase control transformers

(ATEX-tested)
STA: Single-phase control transformer (ATEX-tested)
SteuertrafoSicherheitstrafoTrenntrafoexce

Contact
Tel.: +43 / 2689 / 2744 – 0
E-mail: info@trafomodern.com

Designed and tested according

  • IEC/EN 61558-2-2 / 2-4 / 2-6
  • EN 60079-0
  • EN 60079-7

For use according to

  • EU RL 94/9/EG

Typical applications

  • Control voltage circuit
  • Protective seperation
  • Functional low voltage
  • Safety low voltage

Basic equipment

  • Separate windings
  • Insulation class B
  • Ambient temperature –25 to 40 °C
  • Connection terminal
  • Frequency 50/60 Hz
  • ±5 % tapping on the primary side

Equipment marking

  • II 2 G EEx e II

CAD data

  • According to IEC/EN 61 558 transformers with rated outout voltages ≤ 50 V can be used as safety transformers.

When ordering, the following information must be added to the type designation:

STA0,1(*/*)
1st place holder ≙ rated input voltage
2nd place holder ≙ rated output voltage

Sample order

  • requested type STA0,1
  • requested rated input voltage 230 V
  • requested rated output voltage 36 V

The correct type designation reads STA0,1(230/36)

The unambiguous article number of your configuration will be defined by trafomodern during the offer- and process..

 

Here is a hidden table in the mobile version. Click here to display it.
Rated output Short time rating Rated input voltage Rated output voltage Type Price per unit Cu-no. 1) Copper surcharge
kVA kVA V (selectable) V (selectable)   Euro   Euro
0,1 0,24 50-750 ± 5 % 12-750 STA0,1(*/*) auf Anfrage 0,35 1,75
0,2 0,44     STA0,2(*/*)   0,65 3,26
0,4 1,1     STA0,4(*/*)   1,00 5,01
0,5 1,6     STA0,5(*/*)   1,40 7,02
0,55 1,7     STA0,55(*/*)   1,70 8,52
0,75 2     STA0,75(*/*)   2,10 10,53
1,2 3,7     STA1,2(*/*)   3,20 16,04
1,6 5,5     STA1,6(*/*)   4,70 23,56

1) The calculation method of the material price surcharge will be explained in Section 2.1 in the general conditions of busines.


STA graphic - Single-phase control transformer

The transformer must always be installed in an approved enclosure to with a standardised flameproof rating to EN60079 (in practice "Ex e II" or "Ex p II").

Here is a hidden table in the mobile version. Click here to display it.
Type Total weight No-load losses Short- circuit losses1) Short-circuit voltage Efficiency factor a b c
(WDU 4)
c
(WDU 16)
e f ø g b1 c1
  kg W W %                  
STA0,1 2 6 11 7,5 0,86 85 80 135   64 61 4,8 x 8 74 74,5
STA0,2 3 10 16 5,9 0,89 106 82 153   80,5 61 5,8 x 12 80 94
STA0,4 5,2 18 22 4,1 0,91 121 100 163   90 80 5,8 x 12 98 106
STA0,5 6,8 21 26 3,8 0,91 121 120 163   90 110 5,8 x 12 118 106
STA0,55 7,7 21 25 3,6 0,92 151 107 187 201 122 82 7 x 15 104 132
STA0,75 9,6 24 31 3,3 0,93 151 124 187 201 122 99 7 x 15 121 132
STA1,2 14,9 41 37 2,5 0,94 175 138 210 224 135 110 7 x 15 135 152
STA1,6 17,4 19 38 2,2 0,97 192 142 226 240 150 110 10 x 18 140 170

1) Values measured at room temperature
2) Instead of the split baseplate, STA1,6 has a mounting bracket