Designed and tested according
· IEC/EN 61558-2-6
· UL 5085-2
· CSA 22.2 No. 66
Typical applications
· Control voltage circuits
· Functional low voltage
For use according to
· IEC/EN 60204-1
Basic equipment
· Separate windings
· Insulation class B
· Ambient temperature –25 to 40 °C
· Connection terminal
· Frequency 50/60 Hz
· Single-phase GW units with fuse on the DC side and LED
Other available accessories
· Protective enclosure IP23
· Additional tapping
· Temperature monitoringg
Technical notes
Elektromagnetic compatibility:
- Interference emission Class B, ( EN 55 011, 22 )
- ESD 6 kV contact ( level 3 ) 8 kV air ( level 3 ), IEC/EN 61 000-4-2
- RFI 10 V/m, modulated, IEC/EN 61 000-4-3
- Burst 2 kV ( level 3 ), IEC/EN 61 000-4-4
- Surge 2 kV ( inst.-class 3 ), IEC/EN 61 000-4-5
- Impuls voltage 4,9 kV, IEC/EN 60 947
Environmental data:
- Ambient temperature 25 °C to +55 °C linear charateristic of the Derating Curve from 40° C to 55° C from 100% output to 93% output
- Storage and transport temperature -25 °C to +85 °C
- Degree of soiling 2, EN 50 178
- Vibration 0,0075 mm, ( 10-57 Hz ), 10 Zyklen, IEC 60 068-2-6
- hock 11 ms/15 g, IEC 60 068-2-27, ( 3 shocks )
- Installation altitude max. 2000 m above sea level, if higher: take derating into account
Design input voltage 50/60 Hz V AC | Design output voltage (residual ripple) V DC | Design output current A | Type, Order no. | Price per unit Euro | Cu-factor1) |
---|---|---|---|---|---|
230 | 24 (5 %) | 3 | GW4-030-BA3 4001704 | Price on request | 0,36 |
230 | 24 (5 %) | 5 | GW4-050-BA3 4001705 | 0,37 | |
230 | 24 (5 %) | 8 | GW4-080-BA3 4001706 | 0,82 | |
230 | 24 (5 %) | 10 | GW4-100-BA3 4001707 | 0,96 | |
400 (± 5 %) | 24 (3%) | 5 | GD4-050-BD3 4001699 | 0,65 | |
400 (± 5 %) | 24 (3%) | 10 | GD4-100-BD3 4001700 | 1,12 | |
400 (± 5 %) | 24 (3%) | 15 | GD4-150-BD3 4001701 | 1,30 | |
400 (± 5 %) | 24 (3%) | 20 | GD4-200-BD3 4001702 | 2,10 | |
400 (± 5 %) | 24 (3%) | 30 | GD4-300-BD3 4001703 | 3,00 |
1) The calculation method of the material price surcharge will be explained in Section 2.1 in the general conditions of business.
type | total weight |
no-load losses |
total losses |
residual ripple |
a | b | b1 | c | e | f | g |
---|---|---|---|---|---|---|---|---|---|---|---|
kg | W | W | |||||||||
GD4-050-BD3 | 2,4 | 5 | 27 | < 3 % | 125 | 68 | 61 | 135 | 100 | 45 | 5 |
GD4-100-BD3 | 4,4 | 14,2 | 45 | < 3 % | 155 | 77 | 77 | 165 | 130 | 57 | 8 |
GD4-150-BD3 | 5,8 | 13,9 | 63 | < 3 % | 155 | 92 | 92 | 165 | 130 | 72 | 8 |
GD4-200-BD3 | 7,6 | 25,5 | 89 | < 3 % | 190 | 100 | 83 | 220 | 170 | 58 | 8 |
GD4-300-BD3 | 11,2 | 38,2 | 101 | < 3 % | 190 | 110 | 103 | 235 | 170 | 78 | 8 |
type | U1 | I1 | switch | set current | switch | short-circuit protection only |
---|---|---|---|---|---|---|
V | A | A | ||||
GD 4-050-BD3 | 3 x 400 | 0,24 | PKZM0-0,25 | 0,24 | FAZN S1 | • |
GD 4-100-BD3 | 3 x 400 | 0,46 | PKZM0-0,63 | 0,46 | FAZN S1 | • |
GD 4-150-BD3 | 3 x 400 | 0,65 | PKZM0-1 | 0,65 | FAZN S1 | – |
GD 4-200-BD3 | 3 x 400 | 0,9 | PKZM0-1 | 0,9 | FAZN S1 | – |
GD 4-300-BD3 | 3 x 400 | 1,8 | PKZM0-2,5 | 1,8 | FAZN S2 | – |
1) solid baseplate
2) slotted baseplate
all dimensions in mm