GD – DC POWER SUPPLY UNITS


Designed and tested according

· IEC/EN 61558-2-6
· UL 5085-2
· CSA 22.2 No. 66

Typical applications

· Control voltage circuits
· Functional low voltage

For use according to

· IEC/EN 60204-1

Basic equipment

· Separate windings
· Insulation class B
· Ambient temperature –25 to 40 °C
· Connection terminal
· Frequency 50/60 Hz
· Single-phase GW units with fuse on the DC side and LED

Other available accessories

· Protective enclosure IP23
· Additional tapping
· Temperature monitoringg

Technical notes

Elektromagnetic compatibility:

  • Interference emission Class B, ( EN 55 011, 22 )
  • ESD 6 kV contact ( level 3 ) 8 kV air ( level 3 ), IEC/EN 61 000-4-2
  • RFI 10 V/m, modulated, IEC/EN 61 000-4-3
  • Burst 2 kV ( level 3 ), IEC/EN 61 000-4-4
  • Surge 2 kV ( inst.-class 3 ), IEC/EN 61 000-4-5
  • Impuls voltage 4,9 kV, IEC/EN 60 947

Environmental data:

  • Ambient temperature 25 °C to +55 °C linear charateristic of the Derating Curve from 40° C to 55° C from 100% output to 93% output
  • Storage and transport temperature -25 °C to +85 °C
  • Degree of soiling 2, EN 50 178
  • Vibration 0,0075 mm, ( 10-57 Hz ), 10 Zyklen, IEC 60 068-2-6
  • hock 11 ms/15 g, IEC 60 068-2-27, ( 3 shocks )
  • Installation altitude max. 2000 m above sea level, if higher: take derating into account
Design input voltage 50/60 Hz V AC Design output voltage (residual ripple) V DCDesign output current A Type, Order no. Price per unit Euro Cu-factor1)
230 24 (5 %)3GW4-030-BA3 4001704Price on request0,36
230 24 (5 %)5GW4-050-BA3 40017050,37
230 24 (5 %)8GW4-080-BA3 40017060,82
230 24 (5 %)10GW4-100-BA3 40017070,96
400 (± 5 %) 24 (3%)5GD4-050-BD3 40016990,65
400 (± 5 %) 24 (3%) 10GD4-100-BD3 40017001,12
400 (± 5 %) 24 (3%)15GD4-150-BD3 40017011,30
400 (± 5 %) 24 (3%) 20GD4-200-BD3 40017022,10
400 (± 5 %) 24 (3%)30GD4-300-BD3 40017033,00

1) The calculation method of the material price surcharge will be explained in Section 2.1 in the general conditions of business.

type total
weight
no-load
losses
total
losses
residual
ripple
a b b1 c e f g
kg W W
GD4-050-BD3 2,4 5 27 < 3 % 125 68 61 135 100 45 5
GD4-100-BD3 4,4 14,2 45 < 3 % 155 77 77 165 130 57 8
GD4-150-BD3 5,8 13,9 63 < 3 % 155 92 92 165 130 72 8
GD4-200-BD3 7,6 25,5 89 < 3 % 190 100 83 220 170 58 8
GD4-300-BD3 11,2 38,2 101 < 3 % 190 110 103 235 170 78 8

 

type U1 I1 switch set current switch short-circuit
protection only
V A A
GD 4-050-BD3 3 x 400 0,24 PKZM0-0,25 0,24 FAZN S1
GD 4-100-BD3 3 x 400 0,46 PKZM0-0,63 0,46 FAZN S1
GD 4-150-BD3 3 x 400 0,65 PKZM0-1 0,65 FAZN S1
GD 4-200-BD3 3 x 400 0,9 PKZM0-1 0,9 FAZN S1
GD 4-300-BD3 3 x 400 1,8 PKZM0-2,5 1,8 FAZN S2

1) solid baseplate
2) slotted baseplate
all dimensions in mm