· IEC/EN 61558-2-2 / 2-4 / 2-6
· EN 60079-0
· EN 60079-7
· Control voltage circuit
· Protective seperation
· Functional low voltage
· Safety low voltage
· EU RL 94/9/EG
· Separate windings
· Insulation class B
· Ambient temperature –20 to 40 °C
· Connection terminal
· Frequency 50/60 Hz
· ±5 % tapping on the primary side
· requested type STA0,1
· requested rated input voltage 230 V
· requested rated output voltage 36 V
The correct type designation reads STA0,1(230/36)
The unambiguous article number of your configuration will be defined by trafomodern during the offer- and process.
The transformer must always be installed in an approved enclosure to with a standardised flameproof rating to EN60079.
Technical notes
Equipment marking:
- Ex II 2G Ex eb IIB Gb
Important notes:
According to IEC/EN 61 558 transformers with rated outout voltages ≤ 50 V can be used as safety transformers.When ordering, the following information must be added to the type designation:
- STA0,1(*/*)
- 1st place holder ≙ rated input voltage
- 2nd place holder ≙ rated output voltage
CAD-data
Rated output kVA (<420V) | Short time rating kVA (<420V) | Rated output kVA (>=420V) | Short time rating kVA (>=420V) | Rated input voltage V (selectable) | Rated output voltage V (selectable) | Type | Price per unit Euro | Price per unit A | Cu-no. 1) |
---|---|---|---|---|---|---|---|---|---|
0,1 | 0,24 | 50-750 ± 5 % | 12-750 | STA0,1(*/*) | Price on request | Price on request | 0,35 | ||
0,2 | 0,44 | 50-750 ± 5 % | 12-750 | STA0,2(*/*) | 0,65 | ||||
0,4 | 1,1 | 50-750 ± 5 % | 12-750 | STA0,4(*/*) | 1,00 | ||||
0,5 | 1,6 | 0,45 | 1,44 | 50-750 ± 5 % | 12-750 | STA0,5(*/*) | 1,40 | ||
0,55 | 1,7 | 50-750 ± 5 % | 12-750 | STA0,55(*/*) | 1,70 | ||||
0,75 | 2 | 0,65 | 1,73 | 50-750 ± 5 % | 12-750 | STA0,75(*/*) | 2,10 | ||
1,2 | 3,7 | 50-750 ± 5 % | 12-750 | STA1,2(*/*) | 3,20 | ||||
1,6 | 5,5 | 1,44 | 4,95 | 50-750 ± 5 % | 12-750 | STA1,6(*/*) | 4,70 |
1) The calculation method of the material price surcharge will be explained in Section 2.1 in the general conditions of business.
type | total weight |
no-load losses |
short-circuit losses 1) |
short-circuit voltage |
efficiency | a | b | c (WDU 4) |
c (WDU 16) |
e | f | ø g | b1 | c1 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
kg | W | W | % | |||||||||||
STA0,1 | 2 | 6 | 11 | 7,5 | 0,86 | 85 | 80 | 135 | 64 | 61 | 4,8 x 8 | 74 | 74,5 | |
STA0,2 | 3 | 10 | 16 | 5,9 | 0,89 | 106 | 82 | 153 | 80,5 | 61 | 5,8 x 12 | 80 | 94 | |
STA0,4 | 5,2 | 18 | 22 | 4,1 | 0,91 | 121 | 100 | 163 | 90 | 80 | 5,8 x 12 | 98 | 106 | |
STA0,5 | 6,8 | 21 | 26 | 3,8 | 0,91 | 121 | 120 | 163 | 90 | 110 | 5,8 x 12 | 118 | 106 | |
STA0,55 | 7,7 | 21 | 25 | 3,6 | 0,92 | 151 | 107 | 187 | 201 | 122 | 82 | 7 x 15 | 104 | 132 |
STA0,75 | 9,6 | 24 | 31 | 3,3 | 0,93 | 151 | 124 | 187 | 201 | 122 | 99 | 7 x 15 | 121 | 132 |
STA1,2 | 14,9 | 41 | 37 | 2,5 | 0,94 | 175 | 138 | 210 | 224 | 135 | 110 | 7 x 15 | 135 | 152 |
STA1,62) | 17,4 | 19 | 38 | 2,2 | 0,97 | 192 | 142 | 226 | 240 | 150 | 110 | 10 x 18 | 140 | 170 |
1) Values measured at room temperature
2) Instead of the split baseplate, STA1,6 has a mounting bracket