DTI – Three-phase control, isolation and safety transformers


Designed and tested according

· IEC/EN 61558-2-2 / 2-4 / 2-6
· UL 5085-2
· CSA 22.2 No. 66

Typical applications

· Control voltage circuits
· Functional low voltage
· Safety low voltage
· Protective separation

For use according to

· IEC/EN 60204-1

Basic equipment

· Separate windings
· Insulation class B
· Ambient temperature –25 to 40 °C
· Connection terminal (<=115 A) · Frequency 50/60 Hz · ±5 % tapping on the primary side

Sample order

· requested type DTI0,1
· requested rated input voltage 200 V
· requested rated output voltage 18,5 V
· requested vector group Dy(n)5

The correct type designation reads DTI0,1(200/18,5)Dy(n)5

The unambiguous article number of your configuration will be defined by trafomodern during the offer- and order process

Technical notes

Important notes:

According to IEC/EN 61 558 transformers with rated output voltages ranging from 18.5 V to 42 V can be used as safety transformers.

  • UL/CSA only up to 600 V (incl. tapping)
  • CUR according to UL-File XPTQ2. or XPTQ8.E168819 (Transformers, General Purpose – Component bzw. Transformers, General Purpose Certified for Canada – Component)

When ordering, the following information must be added to the type designation:

  • DTI0,1(*/*)
  • 1st place holder ≙ rated input voltage
  • 2nd place holder ≙ rated output voltage
  • 3rd place holder ≙ vector group

CAD-data

show

Rated output kVA Short time rating kVA Rated input voltage V (selectable) Rated output voltage V (selectable) Type Price per unit Euro Cu-factor 1)
0,10,2200 ± 5 % 18,5 DTI0,1(*/*)* Price on request0,55
0,16 0,32 230 ± 5 % 24 DTI0,16(*/*)* 0,70
0,25 0,5 400 ± 5 %42DTI0,25(*/*)* 1,00
0,4 0,8415 ± 5 % 110DTI0,4(*/*)* 1,10
0,5 1 440 ± 5 % 200 DTI0,5(*/*)* 1,40
0,63 1,38 500 ± 5 % 230 DTI0,63(*/*)* 1,60
1 2,2 690 ± 5 % 400 DTI1,0(*/*)* 2,90
1,6 3,5 DTI1,6(*/*)* 4,40
2 4,4 DTI2,0(*/*)* 6,50
2,5 5,5 DTI2,5(*/*)* 8,60
4 6,2 DTI4,0(*/*)* 9,50
6,3 15,7 DTI6,3(*/*)* 12,00

1) The calculation method of the material price surcharge will be explained in Section 2.1 in the general conditions of business.

 

type total
weight
no-load
losses
short-circuit
losses
short-circuit
voltage
efficiency a b c b c b c b c b c e f ø g b1 c1
kg W W % 18,5 V 24 V 42 V 110 V 230 V
DTI0,1 1,9 5 28 15 0,75 125 65 134 65 134 65 134 65 134 65 134 100 45 5 x 8 61 102
DTI0,16 2,5 8 20 9,5 0,85 125 75 134 75 134 75 134 75 134 75 134 100 55 5 x 8 71 102
DTI0,25 3,6 11 25 8,5 0,88 155 77 154 77 154 77 154 77 154 77 154 130 57 8 x 12 77 128
DTI0,4 5,1 15 40 8 0,88 155 92 154 92 154 92 154 92 154 92 154 130 72 8 x 12 92 128
DTI0,5 6,1 20 35 6 0,9 190 82 180 112 191 82 180 82 180 82 180 170 58 8 x 12 82 155
DTI0,63 8,9 25 50 5,5 0,9 190 102 180 132 191 102 180 102 180 102 180 170 78 8 x 12 102 155
DTI1,0 12,9 35 50 4 0,92 210 137 210 137 210 137 210 117 199 117 199 175 97 8 x 12 117 174
DTI1,6 18,5 55 60 3 0,93 230 144 234 114 269 144 234 114 223 114 223 176 95 7 x 13 114 198
DTI2,0 22,4 60 75 3,5 0,94 240 117 279 117 279 117 279 141 244 117 233 185 95 10 x 18 117 208
DTI2,5 29,3 80 85 2,5 0,94 265 132 299 132 299 132 299 152 264 132 253 200 102 10 x 18 132 228
DTI4,0 39,6 60 100 2 0,96 300 166 317 166 333 147 333 157 296 157 296 224 119 10 x 18 147 260
DTI6,3 50,2 58 170 2 0,96 300 193 285 210 285 193 333 173 333 173 296 224 145 10 x 18 173 260

all dimensions in mm

1) The dimensions of the higher rated voltage are applicable
2) Terminals < 25 A
3) Connection lugs > 63 A